1. Since the return air position inside the equipment is located below the machine, there will be large dirt on the bottom plate that will accumulate in the corners, so please clean it with a vacuum cleaner more than once a week. Please confirm whether the rotation direction of the blower is correct. If you find that the fan rotates in the opposite direction (the wind speed is obviously insufficient), please swap any 2-phase power cords in the three-phase power supply to make sure it rotates in the positive direction.
2. If the air shower cannot automatically sense the shower, check the light sensor system at the lower right corner of the air shower room to see if the light sensor equipment is correct.